Professional Grade

Surge Suppression and

Power Conditioning

Tempest SA3600A Power Conditioning and PLE blocking component (120-240V, 15A)

$155.00

-

An all-wire power conditioner component capable of blocking normal and common mode transients and surge energy as part of a complete electrical enclosure or UPS. The Tempest SA3600 is a wave-shaping and ground filtering device effective in suppressing harmful electrical signal emissions. Protected by U.S. Patent 8,223,468.

In stock (can be backordered)

SKU: SA3600A Category:

Tempest SA3600A Commercial Power Conditioner Component

  • Patented Technology, All-Wire Protection
  • Invented, Patented, Engineered and Manufactured in the USA

For the first time, Bantam Technology is offering our patented and industry-leading surge suppressor/power conditioner/PLE blocking solution, the Tempest SA3600A, as a component.

Application Notes

An all-wire power conditioner component capable of blocking normal and common mode transients and surge energy as part of a complete electrical enclosure or UPS. The Tempest SA3600 is a wave-shaping and ground filtering device effective in suppressing harmful electrical signal emissions. Protected by U.S. Patent 8,223,468.

Features:

  • Supports input power from 120-240 Volts, 15 amps at 50/60 Hertz
  • UL recognized to IEC 62368-1
  • Comes as a Printed Circuit Board Assembly with quick-connect 0.25" lugs for input and output connections
  • Includes our patented surge suppression and ground filtering protection

Key Benefits:

  • Temperature tested at full power to remain under 90 degrees Celsius, so it may not require forced cooling in most applications.
  • The same level and strength of protection as found in the Vanguard PP18004.
  • Ideal for integration with Uninterruptible Power Supplies (UPS), electric welders, PLC and robotics applications and alarm and monitoring equipment installs.

Electrical Ratings:

  • Input and Output connectors: 0.25” QC spades
  • Circuit Protection: User provided
  • Input: 100—240 VAC Single Phase, 50/60 Hz
  • Output: Same as input
  • Maximum Current: 15 Amps
  • Maximum Wattage: 3600 (3.6kW)
  • Regulatory Compliance: UL IEC 62368-1 Component
  • Power Factor: 0.99

Physical Dimensions:

  • H x W x D (mm): 38x52 x153
  • Weight (grams): 300

Performance:

Surge Energy Suppression

    More than 99% of all surge energy is blocked from operating loads during an event. UL 1449 Adjunct testing con- firms full surge protection and no degradation of device or protected equipment after 1280 sequential 6KV/500 8/20us ring-wave injections in a 24-hour period.

Reflected Signal Suppression

    The common mode has a broad resonance at 1 MHz providing approximately 18 dB of insertion loss, with no attenuating effects observed below 10 kHz.  The differential mode has a broad resonance at 1 MHz with continued RF attenuation averaging approximately 25 dB to 30 MHz.

MIL-STD-4561: CS114 Test Results (conducted by NTS Labs, 2018)

    Significant suppression characteristics in the 1 MHz to 20 MHz frequency spectrum, which is commonly known to contain the majority of problematic EMI noise sources in nearly every industry platform.

Harmonics Filtration

    Current harmonic suppression varies based on the load impedance (current draw). In all cases, no suppression of the 60 Hz fundamental current was observed (as expected). Current harmonic suppression is greatest above 1 kHz to 6 kHz.

Additional information

Weight 2 lbs
Dimensions 8 × 6 × 3 in
Bantam Technology by Digilant.net